Avocent PDU
Common Failure (model: PM 3000, shallow & deep versions)
Symptoms:
- No power to devices.
- All PDU LEDs are red.
- PDU displays are blank.
Solution:
Replace internal 12V supply board: XP Power VCP24US12 (Digi-Key Part Number: 1470-2271-ND)
Last modified
8 years ago
Last modified on Oct 14, 2016, 6:09:07 PM
Note:
See TracWiki