Changes between Initial Version and Version 1 of Internal/AvocentPDU
- Timestamp:
- Oct 14, 2016, 6:06:07 PM (8 years ago)
Legend:
- Unmodified
- Added
- Removed
- Modified
-
Internal/AvocentPDU
v1 v1 1 = Avocent PDU = 2 3 == Common Failure (model: PM 3000 small & large) == 4 Symptoms: 5 * No power to devices. 6 * All PDU LEDs are red. 7 * PDU displays are blank. 8 9 Solution: 10 Replace internal 12V supply board: XP Power VCP24US12 (Digi-Key Part Number: [https://www.digikey.com/product-detail/en/xp-power/VCP24US12/1470-2271-ND/4488650 1470-2271-ND])